The outdoor user boundary vacuum load switch is a new type of distribution network automation product developed by our company with the introduction of British Alpine medium-voltage switch technology. The product has the functions of automatic detection of milliampere zero-sequence current faults inside and outside the boundary, protection control and communication. It can automatically cut off single-phase grounding faults and isolate interphase short-circuit faults. The product has a unique design and novel structure, and its performance is ahead of similar domestic products. It is widely used at the responsibility boundary points of 10kV or 6kV overhead distribution lines.

Item

Unit

Remark

Switch body

 

 

Model

FZW28-12F(FFK)

 

Rated voltage

12kV

 

Power frequency insulation withstand voltage (same and relative to ground/break)

42kV/48kV

 

Lightning impulse withstand voltage (same and relative to ground/break)

75kV/85kV(Peak)

 

Rated current

630A

 

Rated short-time withstand current

16kA

 

Rated thermal stability time

2s

 

Rated short-circuit closing current (peak value)

40kA

 

Rated dynamic stability current (peak value)

40kA

 

Rated cable charging breaking current

20A

 

Rated switching no-load transformer inductance current

<5A

 

Mechanical life

10000 time

 

Net weight

180kg

 

Measurement and control unit

 

 

Model

UP400-1

 

Input working voltage

AC220V±20%

 

Input working voltage frequency

50Hz

 

Output voltage (analysis operation)

DC220V

 

Power consumption of the whole machine

<10W

 

Sampling phase current primary input value

120-600A(One-time value)

Adjustable

Low voltage action value

10-140V(Secondary value)

 

Allowable sampling error of power input value

±5%

 

Short circuit protection action delay time value

0.3s

 

Zero sequence current setting value

0-9A(One-time value)

 

Grounding action delay time

0-1200s

Adjustable

Setting value allowable error

±5%

Adjustable

Insulation impedance (external terminal to ground/input terminal to output terminal)

>100MΩ/DC500V

 

Power frequency withstand voltage

2000V/1min

 

Impact withstand voltage

5000V,1.2/50μS Three times each


×